Safety Shower
- Heads
A. Positioned 82″–96″ from floor.
B. Spray pattern will have a minimum diameter of 20″ at 60″ above the floor.
C. Flow Rate=20 gallons (75.71 l) per minute (GPM) of flushing fluid at a velocity low enough to be non-injurious to the user.
D. The center of the spray pattern shall be located at least 16 inches (40.64 cm) from any obstruction.
- Valves
A. Activate in 1 second or less.
B. Stay-open valve (no use of hands).
C. Valve remains on until the user shuts it off.
- Installation
A. Shower shall be located in an area that requires no more than 10 seconds to reach.
B. Shower location shall be in a well-lit area and identified with a sign.
C. The area around the shower shall be painted yellow to remind employees to keep the area clear.
- Maintenance and Training
A. Plumbed showers will be activated weekly to verify correct operation.
B. All employees who might be exposed to a chemical splash shall be trained in the use of the equipment.
C. All showers shall be inspected monthly to make sure they meet with ANSI Z358.1 requirements.